Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

SUBSCRIPTION MANAGEMENT

發(fā)行征訂

首頁(yè) >> 發(fā)行征訂 >> 征訂方式

電流互感器內(nèi)置防開路模塊故障分析與選型策略

來(lái)源:電工電氣發(fā)布時(shí)間:2024-08-01 14:01瀏覽次數(shù):64

電流互感器內(nèi)置防開路模塊故障分析與選型策略

夏鑫,吳秋亮,周世鋼
(江蘇南瑞帕威爾電氣有限公司,江蘇 南京 211100)
 
    摘 要:針對(duì)近年某地區(qū)一起一二次融合 ZW32-12 型柱上斷路器的故障進(jìn)行了技術(shù)分析與試驗(yàn)驗(yàn)證,通過(guò)錄波數(shù)據(jù)查找事故原因,發(fā)現(xiàn)故障發(fā)生的根本原因是電流互感器內(nèi)置防開路模塊啟動(dòng)電壓的設(shè)計(jì)余量小。闡述了防開路模塊的作用和原理,通過(guò)理論計(jì)算和試驗(yàn)驗(yàn)證給出了防開路模塊啟動(dòng)電壓的設(shè)計(jì)依據(jù)。經(jīng)更換合理啟動(dòng)電壓的防開路模塊及時(shí)避免同類故障的再次發(fā)生,提升柱上斷路器的入網(wǎng)質(zhì)量,保障了配網(wǎng)的安全穩(wěn)定運(yùn)行。
    關(guān)鍵詞: 一二次融合柱上斷路器;電流互感器;防開路模塊;伏安特性;選型策略
    中圖分類號(hào):TM452     文獻(xiàn)標(biāo)識(shí)碼:A     文章編號(hào):1007-3175(2024)07-0053-04
 
Fault Analysis and Selection Strategy of Built-In Anti-Open
Circuit Module of Current Transformer
 
XIA Xin, WU Qiu-liang, ZHOU Shi-gang
(Jiangsu NARI Power Electric Co., Ltd, Nanjing 211100, China)
 
    Abstract: In recent years, a primary and secondary fusion ZW32-12 type pole circuit breaker failure was technically analyzed and verified by experiments. The accident cause was searched through the recorded wave data, it was found that the root cause of the fault was the small design margin of the starting voltage of the built-in anti-open circuit module of current transformer. In this paper, the function and principle of anti-open circuit module are briefly described, and the design basis of starting voltage of anti-open circuit module is given through theoretical calculation and experimental verification. Replacing the anti-open circuit module with reasonable starting voltage to avoid the recurrence of similar faults in time, and improve the network access quality of the circuit breaker on the column, thus ensuring the safe and stable operation of the distribution network.
    Key words: primary and secondary fusion column circuit breaker; current transformer; anti-open circuit module; volt-ampere characteristic;selection strategy
 
參考文獻(xiàn)
[1] 蘭劍,王承玉,李慶余. 中國(guó)配電開關(guān)應(yīng)關(guān)注的發(fā)展熱點(diǎn) [J]. 高壓電器,2015,51(10) :217-220.
[2] 王東芳, 黃國(guó)權(quán), 黃廷城, 等. 一二次融合柱上開關(guān)組合加權(quán)模糊狀態(tài)評(píng)價(jià)[J] . 浙江電力,2020,39(2) :48-54.
[3] 王東芳,陶飛達(dá),黃智鵬,等. 一二次融合柱上開關(guān)控制可靠性模型與優(yōu)化設(shè)計(jì)[J] . 高壓電器,2023,59(3) :86-92.
[4] 黃智鵬,熊洽,陳家超,等. 基于改進(jìn)層次分析法的柱上開關(guān)成套設(shè)備狀態(tài)評(píng)估研究[J] . 廣東電力,2020,33(3) :88-94.
[5] 章學(xué)兵,梁亞明,夏震,等. 一起柱上真空斷路器拒動(dòng)故障分析[J]. 電力與能源,2022,43(3) :284-286.
[6] 雷珥梅. CT 伏安特性試驗(yàn)及數(shù)據(jù)分析[C]//2010 年云南電力技術(shù)論壇論文集,2010.